APC Smart-UPS® 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac 2U Rack Mount Uninterruptible Power Supply. 1 Introduction. Sible on the supplied User Manuals CD and on the APC web site, www.apc.com. Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual 3 Introduction Introduction About this UPS The APC Uninterruptible Power Supply (UPS) provides pr otection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic. For installation information, see the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC Web site at www.apc.com. External Battery Pack. For installation information, see the Smart-UPS X 2000-3000 VA External Battery Pack Installation guide that is included with the external battery pack. On this page you find the APC Smart-UPS X 3000VA manual. Please read the instructions in this operator manual carefully before using the product. If you have any questions about your that are not answered in the manual, please share your question in the troubleshooting section on the buttom of this page.

  • #
    28.07.2015458.4 Kb5User Manual 2.pdf
Size:Download

English

APC Smart-UPS

Apc Smart Ups 3000 Manual

1500/3000 VA 120/230 Vac

Modular

Uninterruptible Power Supply

990-170401/2004

Introduction

This APC Smart-UPSis a modular Uninterruptible Power Supply (UPS) for high availability applications such as data centers and mission critical processes, designed to prevent blackouts, brownouts, sags, and surges from reaching your equipment. The UPS filters small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is fully discharged.

1: INSTALLATION

The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC web site, www.apc.com.

Unpack

Attention: Read the safety instruction sheet before installation.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents:

UPS

Bezel

Tower conversion top panels and mounting stabilizers

Rail kit

UPS literature kit containing:

Product documentation, safety,

Serial and USB communication

and warranty information

cables

Smart-UPSUser Manuals CD

230 V models only:

PowerChute® CD

Two input power cords

Network Management Card CD

Four output jumper cords

Mounting hardware

Position the UPS in the Specified Environment

0-40°C

0-95%

1

Mount the UPS in the Rack and Connect the Battery

Attention: Install the rails following the instructions in the rail kit.

Rear

2

How do i find my marriage license online. Tower Configuration

Press and hold the black switch (see location

designation on UPS) to the right while removing the power processing module.

Snap the display bezel out the rear to begin rotation.

Note: Place the UPS in the final operating location prior to module reinstallation.

Rear

3

2: START UP

Connect Equipment to the UPS

Rear Panels

1500 VA, 120 V:

1500 VA, 230 V:

Rackmount

3000 VA, 120 V:

3000 VA, 230 V:

Note:

The ‘outlet groups’ can be controlled through the network software. See Network Management Card documentation.

A laser printer draws significantly more power than other types of equipment and may overload the UPS.

Connect the UPS to the Network (if Applicable)

Network Connectors

Serial Port

USB Port

Ethernet Port

Note:

Use only the supplied cable to connect to the Serial Port. A standard serial interface cable is incompatible with the UPS. Serial and USB ports cannot be used simultaneously.

If an optional Smart-Slotaccessory is to be used, remove the preinstalled network management card and install it now.

Start the UPS

Attention: Upon utility power connection, the UPS will automatically turn on.

1.Plug the UPS into a two-pole,three-wire,grounded receptacle only. Input Plugs:

1500 VA models: 120 V = NEMA5-15P;230 V = Use country specific 10 A with C14 input cords (not supplied).

3000 VA models: 120 V = NEMAL5-30P;230 V = Use the supplied cords or the country specific equivalent.

4

The battery will charge to full capacity during the first few hours of normal operation. Do not expect full ‘on battery’ capability during this initial charge period.

2.After the UPS has ended the immediate self-testwithonline LED illumination, check the front display for any fault indicators (seeTroubleshooting).

3.120 V models: Check thesite wiring fault LED located on the rear panel. It will be illuminated if the UPS is plugged into an improperly wired utility power outlet (seeTroubleshooting).

4.Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is on.

Equipment is now powered and protected. Basic operation, user configuration, and software utilization can now be performed as required.

Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds. Press the button to silence this alarm.

If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

Refer to www.apc.com for battery runtime charts.

When the UPS reaches the low battery shutdown warning (two minute default), the alarm will beep continuously until total shutdown. Connected equipment should be shut down during this time, unless being controlled by network monitoring software.

5

3:BASICOPERATION

Front Display Panel

Apc Smart Ups 3000va Manual

INDICATOR

DESCRIPTION

Online

The UPS is supplying utility power to the connected equipment.

AVR

https://restaurantlucky.netlify.app/autodesk-vault-downloads.html. The UPS is compensating for either a high or low utility voltage.

On Battery

The UPS is supplying battery power to the connected equipment.

Overload

The connected loads are drawing more than the UPS power rating.

Bypass

The connected loads are being powered directly by the utility power connection

and not through the power processing module. This is a fault condition, which

may be caused by an overload or a failure within the module (see Troubleshoot-

ing).

Replace Battery/

The battery is disconnected or must be replaced.

Battery Disconnected

FEATURE

FUNCTION

Power Off

Press this button to turn off the UPS.

6

FEATURE

FUNCTION

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and

every two weeks thereafter (by default). During the self-test,the UPS briefly

operates the connected equipment on battery.

Manual: Press and hold the

button for a few seconds to initiate the self-

test.

Cold Start

Supply battery power to the UPS and connected equipment in the absence of

utility voltage (see Troubleshooting). Press the

button for one second and

release. The UPS will beep briefly and go quiet. Press and hold the button again,

but for approximately three seconds. The unit will emit a sustained beep. Re-

lease the button during this beep.

Diagnostic Utility

The UPS has a diagnostic feature that displays the utility voltage.

Voltage

The UPS starts a self-testas part of this procedure. Theself-testdoes not

affect the voltage display.

Press and hold the

button to view the utility voltage bar graph display.

After a few seconds, this five-LEDbattery charge

display on the right of

the front panel will show the utility input voltage.

Refer to the figure at left for the voltage reading (values are not listed on the

UPS).

The display indicates the voltage is between the displayed value on the list and

the next higher value (see Troubleshooting).

7

4:USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIEDPOWERCHUTE SOFTWARE OR

THE NETWORK INTERFACE CONNECTION. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 14 days

This function sets the interval at which the

(336 hours)

(336 hours),

UPS will execute a self-test.

Every 7 days

(168 hours),

On Startup Only,

No Self-Test

UPS ID

UPS_IDEN

Up to eight characters

Use this field to uniquely identify the UPS,

(i.e. server name or location) for network

management purposes.

Date of Last Battery

Manufacture Date

mm/dd/yy

Reset this date when you replace the inter-

Replacement

nal battery module.

Minimum Capacity

0 percent

0, 15, 30, 45, 60, 75, 90

The UPS will charge its batteries to the

Before Return from

percent

specified percentage before powering up

Shutdown

connected equipment, following a low-

battery shutdown.

Voltage Sensitivity

High

High, Medium, Low

The UPS detects and reacts to line voltage

distortions by transferring to battery power

to protect the connected equipment. When

power quality is poor, the UPS may fre-

quently transfer to battery power. If the

connected equipment can operate normally

under such line voltage conditions, reduce

the sensitivity setting to conserve battery’s

capacity and service life.

Alarm Control

Enable

Enable, Mute, Disable

User can mute an ongoing alarm or disable

all existing alarms permanently.

Shutdown Delay

90 seconds

90, 180, 270, 360, 450,

The interval is set between the times when

540, 630, 0 seconds

the UPS receives a shutdown command and

when it shuts off power to the outlets.

Low Battery Warning

2 minutes

2, 5, 8, 11, 14, 17, 20,

PowerChute software provides automatic,

23 minutes

unattended shutdown when the remaining

battery runtime matches this setting while

on battery.

Change the low battery warning interval

default setting to the time that the operating

system or system software requires to

safely shut down.

Synchronized Turn-on

0 seconds

0, 60, 120, 180, 240,

The UPS will wait the specified time after

Delay

300, 360, 420 seconds

the return of utility power before turn-on

(to avoid branch circuit overload).

8

Size:Download

English

Smart-UPS®RT

3000/5000/6000 VA 200-240Vac

Tower/Rack Mount 3U

Uninterruptible Power Supply

2009 APC by Schneider Electric. APC, the APC logo, Smart-UPSand PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or affiliated companies. All other trademarks are the property of their respective owners.

990-1289E04/2010

Introduction

The APC by Schneider Electric Smart-UPSRT is ahigh-performance,uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

INSTALLATION

Read the Safety Guide before installing the UPS.

Unpacking

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents:

UPS (with battery modules disconnected)

Front bezel

Literature kit containing:

Product documentation, Safety Guide, and Warranty Information

Smart-UPSRT User Manuals CD

Software CD

Serial cable

3000 VA XLI models: three output power cords, two input power cords

Apc Smart Ups 3000 Manual

5000/6000 VA XLI models: six output power cords, Network Management Card documentation

Specifications

TEMPERATURE

This unit is designed for indoor use

OPERATING

32° to 104° F (0° to 40° C)

only. Select a location sturdy enough to

STORAGE

5° to 113° F (-15°to 45° C) charge the UPS

handle the weight.

battery every six months

Do not operate the UPS where there is

MAXIMUM

excessive dust or the temperature and

ELEVATION

humidity are outside the specified limits.

OPERATING

10,000 ft (3,000 m)

Ensure that the air vents on the front

STORAGE

50,000 ft (15,240 m)

and rear of the UPS are not blocked.

HUMIDITY

0 to 95% relative humidity

WEIGHT

UPS

120 lbs (55 kg)

UPS WITH

140 lbs (64 kg)

PACKAGING

.

1

Wiring and Connecting the UPS

5000/6000 VA XLI MODELSONLY: HARDWIRINGINSTRUCTIONS

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker.

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 mm2) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not included).

5.Switch the utility circuit breaker ON.

6.Check line voltages.

7.Replace the access panel.

CONNECTING THEBATTERY MODULES ANDATTACHING THEFRONTBEZEL

.

3

BASICCONNECTORS

Power management software and interface kits can be used with the UPS.

serial com

Use only interface kits supplied or approved by APC.

Any other serial interface cable will be incompatible with the UPS

connector.

Manual bypass enables the user to manually put connected equipment into

bypass mode.

normal bypass

Emergency Power Off terminal allows the user to connect the UPS to the

central EPO system.

EPO terminal

The UPS features a transient voltage surge-suppression(TVSS) screw for

connecting the ground lead on surge suppression devices such as telephone

TVSS screw

and network line protectors.

When connecting grounding cable, disconnect the unit from the utility

power outlet.

Optional external battery packs provide extended runtime during power

outages. These units support up to ten external battery packs.

How do I get a marriage license in Arlington County, Virginia? You will need to visit the Office of the Clerk of the Circuit Court to apply for a marriage license. Both members of the couple must show proof of age, provide valid photo identification, and pay a fee. Alexandria va marriage license. You can find the online marriage license application at Arlington Marriage License. However, you will still need to appear together in person at the County Clerk’s office to sign and pick up your marriage license. Sep 10, 2019  A Clerk of the Circuit Court of Arlington County in Virginia show members of media the form for applying for a marriage license at the Arlington County Courthouse, Oct. 6, 2014 in Arlington, Va. An online pre-application form contains eight standard classifications of race in a drop-down box. Arlington, Fairfax, and Prince William (Manassas) Counties allow you to walk your marriage license back in within five business days of your wedding. The remaining counties require the officiant to mail the license back. Please check with the individual county court clerk’s office for their current marriage license fee. Marriage/Divorce Certificates Marriage and divorce certificates may be obtained by sending an Application For Certification of a Vital Record to the VDH, Office of Vital Records, P.O. Box 1000, Richmond, Virginia 23218.

external battery

See the APC Web site, www.apc.com for the information on the external

pack connector

battery pack, SURT192XLBP.

5000/6000 VA

XLI models

output circuit breakers

3000/5000/6000 VA XLJ/XLT/XLTW models

output circuit breaker

CONNECTINGEQUIPMENT ANDPOWER TO THEUPS

1.Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).

2.Avoid using extension cords.

3000 VA XLJ/XLT/XLTW/XLI and 5000/6000 VA XLJ/XLT/XLTW models: Using a power cord, plug the UPS into a two-pole,three-wire, grounded receptacle only.

5000/6000 VA XLJ and 6000 VA XLT models: To draw full power from the UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel.

3.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.

4.To power up the UPS press the button on the front panel.

The UPS battery charges when it is connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period.

5.For additional computer system security, install PowerChute® Business Edition Smart-UPSmonitoring software.

OPTIONS

Refer to the APC Web site, www.apc.com for available accessories.

External Battery Pack SURT192XLBP

Rail Kit SURTRK2

Isolation Transformer

Service Bypass Panel

.

5

OPERATION

Load

SMART-UPS RT FRONTDISPLAY

Battery Charge

Indicator

Description

Online

The Online LED illuminates when the UPS is drawing utility power and performing

double conversion to supply power to connected equipment.

On Battery

The UPS is supplying battery power to the connected equipment.

Bypass

The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility

power is sent directly to connected equipment during bypass mode operation.

Bypass mode operation is the result of an internal UPS fault, an overload condition

or a user initiated command either through an accessory or the manual bypass

switch. Battery operation is not available while the UPS is in bypass mode. Refer to

Troubleshooting in this manual.

Fault

The UPS detects an internal fault.

Refer to Troubleshooting in this manual.

Overload

An overload condition exists. See Troubleshooting.

Replace

The battery is disconnected or must be replaced. See Troubleshooting.

Battery

Feature

Function

Power On

Press this button to turn on the UPS. (See below for additional capabilities.)

Power Off

Press this button to turn off the UPS.

Feature

Function

Cold Start

When there is no utility power and the UPS is off, press and hold the

button to

power up the UPS and connected equipment.

The UPS will emit two beeps. During the second beep, release the button.

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and every

two weeks thereafter (by default). During the self-test,the UPS briefly operates the

connected equipment on battery.

Manual: Press and hold the

button for a few seconds to initiate the self-test.

Diagnostic Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. Plug

the UPS into the normal utility power.

The UPS starts a self-testas part of this procedure. Theself-test

does not affect the voltage display.

Press and hold the

button to view the utility voltage bar graph

display. After a few seconds the five-LED,Battery Charge

display

on the right of the front panel shows the utility input voltage.

Refer to the figure at left for the voltage reading (values are not listed

on the UPS).

The display indicates the voltage is between the displayed value on the

list and the next higher value.

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When 2 minutes of run time remain the UPS emits a continuous beeping. If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully discharges the battery.

The UPS battery life differs based on usage and environment. Refer to www.apc.com, for on battery runtimes.

.

7

USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OPTIONALSMARTSLOT ACCESSORY CARDS ORTERMINALMODE.

Apc Smart Ups 3000 Rm Manual

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 7 days(168 hours),

Set the interval at which the

(336 hours)

14 days (336 hours)

UPS will execute a self-test.

On Startup Only,

No Self-Test

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

define the UPS

server name or location) for

network management purposes.

Date of Last Battery

Manufacture Date

Date of

Reset this date when you replace

Replacement

Battery Replacement

the battery modules.

Intel 855gm windows 7. mm/dd/yy

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Following a low-battery

Before Return from

90 percent

shutdown, the battery modules

The reason that initials do not lead to recognition is that the human mind works by sounds, not by spellings.Most companies began selling a single product, and the name of the company usually reflected that product. Jack trout positioning pdf. Ries and Trout advise managers who aspire for name recognition to use an actual name rather then first and middle initials.

Shutdown

will be charged to the specified

percentage before powering

connected equipment.

Alarm Delay After

5 second delay

5 or 30 second delay

Mute ongoing alarms or disable

Line Failure

At Low Battery

all alarms permanently.

Never

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

720, 960 seconds

when the UPS receives a

shutdown command and the

actual shutdown.

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes

are continuous when two

software provides

minutes of run time remain.

automatic,

Change the warning interval

unattended

default to a higher setting if the

shutdown when

operating system requires a

approximately 2

longer interval for shutdown.

minutes of battery

operated runtime

remains.

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

The UPS will wait the specified

Delay

720, 960 seconds

time after the return of utility

power before turn-on(to avoid

branch circuit overload).

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

output voltage

+20%

will pass to connected

setting

equipment during internal

bypass operation.